CVE-2016-4784

MEDIUM

Siemens Siprotec Firmware - Information Disclosure

Title source: rule

Description

A vulnerability has been identified in firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02; SIPROTEC 7SJ686 : All versions < V 4.83; SIPROTEC 7UT686 : All versions < V 4.01; SIPROTEC 7SD686 : All versions < V 4.03; SIPROTEC 7SJ66 : All versions < V 4.20. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain sensitive device information if network access was obtained.

Scores

CVSS v3 5.3
EPSS 0.0240
EPSS Percentile 84.9%
Attack Vector NETWORK
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N

Classification

CWE
CWE-200
Status draft

Affected Products (2)

siemens/siprotec_firmware
siemens/siprotec_firmware

Timeline

Published May 31, 2016
Tracked Since Feb 18, 2026