CVE-2017-14464
CRITICALAllen Bradley Micrologix 1400 Series B FRN 21.2 - Info Disclosure
Title source: llmDescription
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability.Required Keyswitch State: REMOTE or PROG Associated Fault Code: 0001 Fault Type: Non-User Description: A fault state can be triggered by setting the NVRAM/memory module user program mismatch bit (S2:9) when a memory module is NOT installed.
References (1)
Core 1
Core References
Exploit, Third Party Advisory x_refsource_misc
https://www.talosintelligence.com/vulnerability_reports/TALOS-2017-0443
Scores
CVSS v3
9.8
EPSS
0.3695
EPSS Percentile
97.2%
Attack Vector
NETWORK
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Details
Status
published
Products (1)
rockwellautomation/micrologix_1400_b_firmware
< 21.2
Published
Apr 05, 2018
Tracked Since
Feb 18, 2026