CVE-2020-15791

MEDIUM

Siemens Simatic S7-300 Cpu 312 Firmware - Insufficiently Protected ...

Title source: rule

Description

A vulnerability has been identified in SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC S7-400 CPU family (incl. SIPLUS variants) (All versions), SIMATIC WinAC RTX (F) 2010 (All versions), SINUMERIK 840D sl (All versions). The authentication protocol between a client and a PLC via port 102/tcp (ISO-TSAP) insufficiently protects the transmitted password. This could allow an attacker that is able to intercept the network traffic to obtain valid PLC credentials.

Scores

CVSS v3 6.5
EPSS 0.0008
EPSS Percentile 23.8%
Attack Vector ADJACENT_NETWORK
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

Classification

CWE
CWE-522
Status published

Affected Products (14)

siemens/simatic_s7-300_cpu_312_firmware
siemens/simatic_s7-300_cpu_314_firmware
siemens/simatic_s7-300_cpu_315-2_dp_firmware
siemens/simatic_s7-300_cpu_315-2_pn_firmware
siemens/simatic_s7-300_cpu_317-2_pn_firmware
siemens/simatic_s7-300_cpu_317-2_dp_firmware
siemens/simatic_s7-300_cpu_315f-2_dp_firmware
siemens/simatic_s7-300_cpu_315f-2_pn_firmware
siemens/simatic_s7-300_cpu_317f-2_pn_firmware
siemens/simatic_s7-300_cpu_317f-2_dp_firmware
siemens/simatic_s7-400_cpu_412_firmware
siemens/simatic_s7-400_cpu_414_firmware
siemens/simatic_s7-400_cpu_416_firmware
siemens/simatic_s7-400_cpu_417_firmware

Timeline

Published Sep 09, 2020
Tracked Since Feb 18, 2026