Description

Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x includes the functionality of setting a password that is required to execute privileged commands. The password value passed to ISaGRAF Runtime is the result of encryption performed with a fixed key value using the tiny encryption algorithm (TEA) on an entered or saved password. A remote, unauthenticated attacker could pass their own encrypted password to the ISaGRAF 5 Runtime, which may result in information disclosure on the device.

References (4)

Core 4

Scores

CVSS v3 5.3
EPSS 0.0010
EPSS Percentile 27.6%
Attack Vector NETWORK
CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:N/A:N

CISA SSVC

Vulnrichment
Exploitation none
Automatable no
Technical Impact partial

Details

CWE
CWE-321 CWE-798
Status published
Products (20)
rockwellautomation/aadvance_controller < 1.40
rockwellautomation/isagraf_free_runtime < 6.6.8
rockwellautomation/isagraf_runtime 5.0 - 6.0
rockwellautomation/micro810_firmware
rockwellautomation/micro820_firmware
rockwellautomation/micro830_firmware
rockwellautomation/micro850_firmware
rockwellautomation/micro870_firmware
schneider-electric/easergy_c5_firmware < 1.1.0
schneider-electric/easergy_t300_firmware < 2.7.1
... and 10 more