CVE-2020-7575

MEDIUM

Climatix POL908 and POL909 < V11.32 - Stored Cross-Site Scripting via Web Server Access Log Page

Title source: llm
STIX 2.1

Description

A vulnerability has been identified in Climatix POL908 (BACnet/IP module) (All versions), Climatix POL909 (AWM module) (All versions < V11.32). A persistent cross-site scripting (XSS) vulnerability exists in the web server access log page of the affected devices that could allow an attacker to inject arbitrary JavaScript code via specially crafted GET requests. The code could be potentially executed later by another (privileged) user. The security vulnerability could be exploited by an attacker with network access to the affected system. Successful exploitation requires no system privileges. An attacker could use the vulnerability to compromise the confidentiality and integrity of other users' web sessions.

References (1)

Core 1
Core References

Scores

CVSS v3 6.1
EPSS 0.0037
EPSS Percentile 59.1%
Attack Vector NETWORK
CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N

Details

CWE
CWE-80 CWE-79
Status published
Products (2)
siemens/climatix_pol908_firmware
siemens/climatix_pol909_firmware < 11.32
Published Apr 14, 2020
Tracked Since Feb 18, 2026