CVE-2020-7580

MEDIUM

SIMATIC Automation Tool < V4 SP2 - Unquoted Search Path or Element

Title source: llm
STIX 2.1

Description

A vulnerability has been identified in SIMATIC Automation Tool (All versions < V4 SP2), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC NET PC Software V16 (All versions < V16 Upd3), SIMATIC PCS neo (All versions < V3.0 SP1), SIMATIC ProSave (All versions < V17), SIMATIC S7-1500 Software Controller (All versions < V21.8), SIMATIC STEP 7 (TIA Portal) V13 (All versions < V13 SP2 Update 4), SIMATIC STEP 7 (TIA Portal) V14 (All versions < V14 SP1 Update 10), SIMATIC STEP 7 (TIA Portal) V15 (All versions < V15.1 Update 5), SIMATIC STEP 7 (TIA Portal) V16 (All versions < V16 Update 2), SIMATIC STEP 7 V5 (All versions < V5.6 SP2 HF3), SIMATIC WinCC OA V3.16 (All versions < V3.16 P018), SIMATIC WinCC OA V3.17 (All versions < V3.17 P003), SIMATIC WinCC Runtime Advanced (All versions < V16 Update 2), SIMATIC WinCC Runtime Professional V13 (All versions < V13 SP2 Update 4), SIMATIC WinCC Runtime Professional V14 (All versions < V14 SP1 Update 10), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Update 5), SIMATIC WinCC Runtime Professional V16 (All versions < V16 Update 2), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 14), SIMATIC WinCC V7.5 (All versions < V7.5 SP1 Update 3), SINAMICS STARTER (All Versions < V5.4 HF2), SINAMICS Startdrive (All Versions < V16 Update 3), SINEC NMS (All versions < V1.0 SP2), SINEMA Server (All versions < V14 SP3), SINUMERIK ONE virtual (All Versions < V6.14), SINUMERIK Operate (All Versions < V6.14). A common component used by the affected applications regularly calls a helper binary with SYSTEM privileges while the call path is not quoted. This could allow a local attacker to execute arbitrary code with SYTEM privileges.

References (2)

Core 2
Core References
Third Party Advisory, US Government Resource
https://us-cert.cisa.gov/ics/advisories/icsa-20-161-04

Scores

CVSS v3 6.7
EPSS 0.0005
EPSS Percentile 15.3%
Attack Vector LOCAL
CVSS:3.1/AV:L/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H

Details

CWE
CWE-428
Status published
Products (22)
siemens/simatic_automatic_tool
siemens/simatic_net_pc 16 (2 CPE variants)
siemens/simatic_net_pc < 16
siemens/simatic_pcs_7
siemens/simatic_pcs_neo
siemens/simatic_prosave
siemens/simatic_s7-1500_software_controller < 21.8
siemens/simatic_step_7 5.6 (4 CPE variants)
siemens/simatic_step_7 < 5.6
siemens/simatic_wincc 7.4 (15 CPE variants)
... and 12 more
Published Jun 10, 2020
Tracked Since Feb 18, 2026