CVE-2021-32986

CRITICAL

Automation Direct CLICK PLC CPU <3.00 - Privilege Escalation

Title source: llm
STIX 2.1

Description

After Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 is unlocked by an authorized user, the unlocked state does not timeout. If the programming software is interrupted, the PLC remains unlocked. All subsequent programming connections are allowed without authorization. The PLC is only relocked by a power cycle, or when the programming software disconnects correctly.

References (1)

Core 1
Core References
Third Party Advisory, US Government Resource x_refsource_confirm
https://www.cisa.gov/uscert/ics/advisories/icsa-21-166-02

Scores

CVSS v3 9.8
EPSS 0.0104
EPSS Percentile 59.4%
Attack Vector NETWORK
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

CISA SSVC

Vulnrichment
Exploitation none
Automatable yes
Technical Impact total

Details

CWE
CWE-288 CWE-863
Status published
Products (20)
automationdirect/c0-10are-d_firmware < 3.00
automationdirect/c0-10dd1e-d_firmware < 3.00
automationdirect/c0-10dd2e-d_firmware < 3.00
automationdirect/c0-10dre-d_firmware < 3.00
automationdirect/c0-11are-d_firmware < 3.00
automationdirect/c0-11dd1e-d_firmware < 3.00
automationdirect/c0-11dd2e-d_firmware < 3.00
automationdirect/c0-11dre-d_firmware < 3.00
automationdirect/c0-12are-1-d_firmware < 3.00
automationdirect/c0-12are-2-d_firmware < 3.00
... and 10 more
Published Apr 04, 2022
Tracked Since Feb 18, 2026