CVE-2021-32986
CRITICALAutomation Direct CLICK PLC CPU <3.00 - Privilege Escalation
Title source: llmDescription
After Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 is unlocked by an authorized user, the unlocked state does not timeout. If the programming software is interrupted, the PLC remains unlocked. All subsequent programming connections are allowed without authorization. The PLC is only relocked by a power cycle, or when the programming software disconnects correctly.
References (1)
Core 1
Core References
Third Party Advisory, US Government Resource x_refsource_confirm
https://www.cisa.gov/uscert/ics/advisories/icsa-21-166-02
Scores
CVSS v3
9.8
EPSS
0.0104
EPSS Percentile
59.4%
Attack Vector
NETWORK
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
CISA SSVC
Vulnrichment
Exploitation
none
Automatable
yes
Technical Impact
total
Details
CWE
CWE-288
CWE-863
Status
published
Products (20)
automationdirect/c0-10are-d_firmware
< 3.00
automationdirect/c0-10dd1e-d_firmware
< 3.00
automationdirect/c0-10dd2e-d_firmware
< 3.00
automationdirect/c0-10dre-d_firmware
< 3.00
automationdirect/c0-11are-d_firmware
< 3.00
automationdirect/c0-11dd1e-d_firmware
< 3.00
automationdirect/c0-11dd2e-d_firmware
< 3.00
automationdirect/c0-11dre-d_firmware
< 3.00
automationdirect/c0-12are-1-d_firmware
< 3.00
automationdirect/c0-12are-2-d_firmware
< 3.00
... and 10 more
Published
Apr 04, 2022
Tracked Since