CVE-2022-2502
HIGHHitachiEnergy RTU500 Firmware - Denial of Service via Crafted IEC 60870-5-104 Message
Title source: llmDescription
A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.
References (2)
Core 2
Core References
Various Sources vendor-advisory
https://publisher.hitachienergy.com/preview?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch
Scores
CVSS v3
7.5
EPSS
0.0054
EPSS Percentile
41.3%
Attack Vector
NETWORK
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
CISA SSVC
Vulnrichment
Exploitation
none
Automatable
yes
Technical Impact
partial