CVE-2023-2071

CRITICAL

Rockwell Automation FactoryTalk View < 13.0 - Unauthenticated Remote Code Execution via CIP Class Library Upload

Title source: llm
STIX 2.1

Description

Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets.  The device has the functionality, through a CIP class, to execute exported functions from libraries.  There is a routine that restricts it to execute specific functions from two dynamic link library files.  By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.

References (1)

Core 1

Scores

CVSS v3 9.8
EPSS 0.1097
EPSS Percentile 95.3%
Attack Vector NETWORK
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

CISA SSVC

Vulnrichment
Exploitation none
Automatable no
Technical Impact partial

Details

CWE
CWE-20 CWE-434
Status published
Products (1)
rockwellautomation/factorytalk_view < 13.0
Published Sep 12, 2023