CVE-2023-39464
HIGHTrianglemicroworks Scada Data Gateway - Remote Code Execution
Title source: ruleDescription
Triangle MicroWorks SCADA Data Gateway GTWWebMonitorService Unquoted Search Path Remote Code Execution Vulnerability. This vulnerability allows remote attackers to execute code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed. The specific flaw exists within the configuration of the GTWWebMonitorService service. The path to the service executable contains spaces not surrounded by quotations. An attacker can leverage this vulnerability to execute arbitrary code in the context of root. Was ZDI-CAN-20538.
Scores
CVSS v3
7.2
EPSS
0.0023
EPSS Percentile
45.7%
Attack Vector
NETWORK
CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H
CISA SSVC
Vulnrichment
Exploitation
none
Automatable
no
Technical Impact
total
Details
CWE
CWE-428
Status
published
Products (1)
trianglemicroworks/scada_data_gateway
5.1.3.20324
Published
May 03, 2024
Tracked Since