CVE-2025-3756

MEDIUM

Denial of Service Vulnerabilities in System 800xA, Symphony® Plus IEC 61850

Title source: cna
STIX 2.1

Description

A vulnerability exists in the command handling of the IEC 61850 communication stack included in the product revisions listed as affected in this CVE. An attacker with access to IEC 61850 networks could exploit the vulnera bility by using a specially crafted 61850 packet, forcing the communication interfaces of the PM 877, CI850 and CI868 modules into fault mode or causing unavailability of the S+ Operations 61850 connectivity, resulting in a denial-of-service situation.  The System 800xA IEC61850 Connect is not affected. Note: This vulnerability does not impact on the overall availability and functionality of the S+ Operations node, only the 61850 communication function.     This issue affects AC800M (System 800xA): from 6.0.0x through 6.0.0303.0, from 6.1.0x through 6.1.0031.0, from 6.1.1x through 6.1.1004.0, from 6.1.1x through 6.1.1202.0, from 6.2.0x through 6.2.0006.0; Symphony Plus SD Series: A_0, A_1, A_2.003, A_3.005, A_4.001, B_0.005; Symphony Plus MR (Melody Rack): from 3.10 through 3.52; S+ Operations: 2.1, 2.2, 2.3, 3.3.

Scores

CVSS v3 6.5
EPSS 0.0003
EPSS Percentile 6.8%
Attack Vector ADJACENT_NETWORK
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

CISA SSVC

Vulnrichment
Exploitation none
Automatable no
Technical Impact partial

Details

CWE
CWE-1284
Status published
Products (16)
ABB/AC800M (System 800xA) 6.0.0x - 6.0.0303.0
ABB/AC800M (System 800xA) 6.1.0x - 6.1.0031.0
ABB/AC800M (System 800xA) 6.1.1x - 6.1.1004.0
ABB/AC800M (System 800xA) 6.1.1x - 6.1.1202.0
ABB/AC800M (System 800xA) 6.2.0x - 6.2.0006.0
ABB/S+ Operations 2.1
ABB/S+ Operations 2.2
ABB/S+ Operations 2.3
ABB/S+ Operations 3.3
ABB/Symphony Plus MR (Melody Rack) 3.10 - 3.52
... and 6 more
Published Apr 13, 2026
Tracked Since Apr 13, 2026