CVE-2025-40944

HIGH

SIMATIC ET 200AL IM 157-1 PN - Denial of Service via S7 Protocol Disconnect Request

Title source: llm
STIX 2.1

Description

A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0 < V4.2.5), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state. This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.

References (1)

Core 1

Scores

CVSS v3 7.5
EPSS 0.0040
EPSS Percentile 31.3%
Attack Vector NETWORK
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

CISA SSVC

Vulnrichment
Exploitation none
Automatable yes
Technical Impact partial

Details

CWE
CWE-400
Status published
Products (19)
Siemens/SIMATIC ET 200AL IM 157-1 PN
Siemens/SIMATIC ET 200MP IM 155-5 PN HF V4.2.0
Siemens/SIMATIC ET 200SP IM 155-6 MF HF
Siemens/SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) < V1.3
Siemens/SIMATIC ET 200SP IM 155-6 PN R1 < V6.0.1
Siemens/SIMATIC ET 200SP IM 155-6 PN/2 HF V4.2.0
Siemens/SIMATIC ET 200SP IM 155-6 PN/2 HF V4.2.0 - V4.2.5
Siemens/SIMATIC ET 200SP IM 155-6 PN/3 HF < V4.2.2
Siemens/SIMATIC PN/MF Coupler
Siemens/SIMATIC PN/PN Coupler < V6.0.0
... and 9 more
Published Jan 13, 2026
Tracked Since Feb 18, 2026